Emergency Response & System Restoration Procedures Flashcards

7 cards from real SOPD practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Emergency Response & System Restoration Procedures flashcards as text
  1. During a widespread blackout, what is the correct sequence for restoring the transmission system?

    Answer: Restore generation, establish transmission backbone, then pick up load

    The standard black start sequence establishes generation and transmission backbone first before incrementally picking up customer load to avoid overloads.

  2. A synchronizing check relay (25) prevents closing a breaker when:

    Answer: The frequency difference between two systems exceeds the relay's set threshold

    A sync-check relay monitors voltage magnitude, angle, and frequency difference, blocking closure when the differential exceeds its permitted threshold to prevent a damaging out-of-phase close.

  3. What is 'islanding' in power system context during an emergency?

    Answer: A portion of the system operating isolated from the main grid, potentially with uncontrolled frequency

    Islanding occurs when a section of the power grid continues to operate independently after separation from the main grid, which can create unsafe frequency and voltage conditions.

  4. Under NERC EOP-005, what must operators verify before energizing a transmission line during restoration?

    Answer: That protection systems are in service and the line is clear of work tags

    EOP-005 requires operators to confirm protection systems are in service and the element is free of clearances/tags before energizing during system restoration.

  5. When frequency drops below the first stage of an Under-Frequency Load Shedding (UFLS) scheme, the scheme automatically:

    Answer: Disconnects a pre-set block of customer load to arrest the frequency decline

    UFLS automatically trips pre-programmed load blocks to reduce demand and arrest frequency decline when it falls below defined thresholds.

  6. A system operator notices bus voltage is 8% below scheduled level during an emergency. The FIRST corrective action should be:

    Answer: Raise generation reactive output (MVAr) and check capacitor bank status

    Low voltage is primarily corrected by increasing reactive power supply — raising generator excitation or switching in capacitor banks — before resorting to load shedding.

  7. During black start restoration, why is it important to control the rate of load pickup?

    Answer: To avoid excessive frequency dips that could trip the black start unit off-line

    Adding load too fast causes frequency to dip; if the dip is large enough it can trip the black start generator on under-frequency, losing the restoration anchor.