Hardware Architecture & Fault Tolerance Flashcards

7 cards from real SIL practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Hardware Architecture & Fault Tolerance flashcards as text
  1. What does Hardware Fault Tolerance (HFT) represent in a safety-related subsystem?

    Answer: The number of faults a subsystem can withstand while maintaining its safety function

    HFT = N means the subsystem can tolerate N faults and still perform its required safety function.

  2. According to IEC 61508, how is a 'Type A' subsystem characterized?

    Answer: A subsystem in which failure modes of all components are well defined and can be fully enumerated

    Type A subsystems have well-defined, fully enumerable failure modes for all components, distinguishing them from the more complex Type B.

  3. Which statement correctly describes Safe Failure Fraction (SFF) per IEC 61508?

    Answer: The fraction of total failures that are either safe failures or dangerous but detected failures

    SFF = (λS + λDD) / (λS + λDD + λDU), combining safe and detected dangerous failure rates as a fraction of all failures.

  4. What is the Hardware Fault Tolerance of a 1oo2 (1-out-of-2) voting architecture?

    Answer: HFT = 1

    In 1oo2, one channel can fail while the other still initiates the safety action, so the system tolerates one fault — HFT = 1.

  5. Why is a 2oo3 voting architecture commonly preferred over 1oo2 in process safety applications?

    Answer: It reduces spurious trips compared to 1oo2 while still maintaining HFT = 1

    2oo3 requires agreement from two channels for the safety action, reducing spurious trips versus 1oo2, while a single failure still leaves two channels able to act (HFT = 1).

  6. What is the primary purpose of architectural constraints defined in IEC 61508-2?

    Answer: To set minimum hardware redundancy requirements based on target SIL and subsystem type

    Architectural constraints in IEC 61508-2 Tables 2 and 3 mandate minimum HFT values based on the target SIL and whether the subsystem is Type A or Type B.

  7. In safety architecture notation, what does the 'D' suffix signify in a 1oo1D configuration?

    Answer: Diagnostics are incorporated to detect and respond to dangerous failures

    The 'D' in 1oo1D denotes that diagnostic coverage is used to detect dangerous failures and initiate a safe response, compensating for the lack of hardware redundancy.