Electrical System Design & Installation Flashcards
7 cards from real PC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Electrical System Design & Installation flashcards as text
A 480V, 3-phase transformer has a 75 kVA rating. What is the full-load secondary current for a 208Y/120V secondary?
Answer: 208A
FLA = kVA × 1000 ÷ (√3 × V) = 75,000 ÷ (1.732 × 208) = 75,000 ÷ 360.3 ≈ 208A.
Per NEC 210.52(C), receptacle outlets in a kitchen must be installed so that no point along the countertop wall space is more than how far from a receptacle?
Answer: 24 inches
NEC 210.52(C)(1) requires that no point along a kitchen countertop wall space be more than 24 inches from a receptacle outlet.
What protection is required for all 125V through 250V receptacles installed in a crawl space at or below grade level?
Answer: GFCI protection
NEC 210.8(A)(4) requires GFCI protection for receptacles in crawl spaces at or below grade level due to moisture hazards.
When installing EMT in a concrete slab, what NEC requirement applies to the minimum concrete cover?
Answer: 2 inch minimum cover
Per NEC 358.10(B) and 300.6(D), EMT embedded in concrete must have at least 2 inches of concrete cover unless listed for less.
A load center in a residential garage must have its panelboard mounted at what maximum height per the NEC?
Answer: 6 feet 7 inches to the center of the highest breaker
NEC 240.24(A) requires that the center of the grip of the operating handle of a breaker, when in its highest position, not exceed 6 feet 7 inches above the floor.
What is the minimum size equipment grounding conductor (EGC) required for a circuit protected by a 100A overcurrent device per NEC Table 250.122?
Answer: #8 AWG copper
Per NEC Table 250.122, a 100A overcurrent device requires a minimum #8 AWG copper equipment grounding conductor.
Which wiring method is specifically listed by the NEC as suitable for direct burial without conduit protection?
Answer: USE-2 cable
USE-2 (Underground Service Entrance) cable is rated and listed for direct burial applications without requiring conduit.