← All NATE Flashcard Decks

Oil Heating Flashcards

6 cards from real NATE practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Oil Heating flashcards as text
  1. What component in an oil burner atomizes the fuel oil and mixes it with air for combustion?

    Answer: Nozzle

    The nozzle atomizes oil into a fine spray at a precise angle and pattern, mixing it with combustion air for efficient burning.

  2. What is the function of the cad cell (cadmium sulfide cell) in an oil burner primary control?

    Answer: Sense the presence or absence of a flame by its resistance to light

    The cad cell changes resistance based on light; in darkness (no flame) its high resistance signals the primary control to initiate lockout.

  3. What is the primary control's 'safety timing' function on an oil furnace?

    Answer: Allow a limited time for ignition then shut down the burner if no flame is proven

    Safety timing (typically 45–90 seconds) limits how long unburned oil can accumulate before locking out the burner to prevent explosion.

  4. What annual maintenance item is most critical for oil burner efficiency?

    Answer: Replacing the nozzle and cleaning the strainer, electrodes, and heat exchanger

    An annual tune-up including nozzle replacement and cleaning ensures complete combustion, maximum efficiency, and safe operation.

  5. What does a smoke tester (Bacharach pump) measure on an oil burner?

    Answer: Carbon soot level in flue gases by comparing a filter paper sample to a standard scale

    The smoke tester draws flue gas through filter paper; the resulting stain is compared to a numbered scale (0 = clean, 9 = heavy smoke).

  6. What is the typical oil pump pressure setting for a residential oil burner?

    Answer: 100–150 PSI

    Residential oil burner pumps typically operate at 100–150 PSI (commonly 100 PSI) to properly atomize the fuel through the nozzle.