Power Cable Test Methods Flashcards
7 cards from real NETA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Power Cable Test Methods flashcards as text
In a DC hipot test, which component of leakage current is most indicative of insulation condition?
Answer: Resistive (conduction) leakage current
The resistive component represents true conduction through the insulation and reflects the insulation's dielectric quality; capacitive current decays after initial charging.
What minimum insulation resistance value does NETA MTS typically cite for 600 V rated cables in field maintenance testing?
Answer: 1 MΩ
NETA maintenance tables set a minimum acceptance threshold of 1 MΩ for low-voltage insulation; values below warrant investigation.
What is the significance of the Polarization Index (PI) in cable insulation testing?
Answer: Ratio of 10-minute IR to 1-minute IR, indicating insulation dryness and integrity
The PI is the ratio of the 10-minute IR to the 1-minute IR; values above 2.0 for most insulation types indicate acceptable dryness and integrity.
During a TDR test, a reflected pulse arrives back sooner than expected for the cable's known length. What does this indicate?
Answer: There is an open-circuit fault closer to the test end than the far end
A reflection arriving earlier than the far-end open means an impedance discontinuity (fault) exists at a shorter distance along the cable.
Why is DC hipot testing generally discouraged for service-aged XLPE cables per IEEE 400?
Answer: DC stress can cause space charge buildup that damages water-treed XLPE insulation
Space charge accumulation in aged XLPE under DC stress can cause localized field enhancement that leads to breakdown, making DC hipot potentially destructive.
Which parameter measured during a VLF tan delta test indicates early-stage water treeing in XLPE cable?
Answer: A rising tan delta value with increasing test voltage (tip-up)
Voltage-dependent increase in tan delta (tip-up) is a classic signature of water tree degradation in XLPE cable insulation.
What safety action must be performed on a test cable immediately after completing a DC hipot test?
Answer: Slowly discharge the cable through a resistor and verify zero voltage before touching
Cable capacitance stores charge at the full test voltage; it must be discharged slowly through a resistor and then verified with a voltmeter before personnel contact.