← All NETA Flashcard Decks

Motor and Generator Testing Flashcards

6 cards from real NETA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Motor and Generator Testing flashcards as text
  1. During generator commissioning, the synchronizing check relay (Device 25) function verifies that before closing to the grid:

    Answer: The generator voltage magnitude, frequency, and phase angle match the bus within acceptable tolerances before closing the circuit breaker

    Synchronizing check relays prevent closing a generator breaker unless voltage magnitude, frequency, and phase angle are within acceptable windows to prevent the sudden power surge from an out-of-synchronism close.

  2. The purpose of a generator stator core iron test (EL-CID test) is to:

    Answer: Detect localized shorted laminations in the stator core that cause eddy current hotspots

    The EL-CID (Electromagnetic Core Imperfection Detector) test excites the stator core to approximately 4% rated flux and uses a search coil to detect localized high-current spots from shorted laminations, which cause hotspots during normal operation.

  3. A motor's service factor (SF) listed on the nameplate indicates:

    Answer: The permissible overload factor: a 1.15 SF motor can operate continuously at 15% above nameplate kW

    Service factor is a multiplier applied to nameplate horsepower/kW indicating allowable continuous overload. SF = 1.15 means the motor can run at 115% of rated load continuously, with higher temperature rise.

  4. What is the significance of critical speed in large motor and generator applications?

    Answer: A rotor speed at which the rotational frequency coincides with a natural mechanical resonant frequency, causing excessive vibration

    Critical speed is the rotor speed that matches a natural lateral mechanical resonance frequency of the rotor-shaft-bearing system, causing resonant vibration amplification that can cause catastrophic damage if sustained.

  5. Excitation current testing of a synchronous generator with no load measures the field current required to produce rated terminal voltage. An increase in required excitation current compared to factory data may indicate:

    Answer: Increased air gap due to bearing wear or rotor movement, or demagnetization of the rotor poles

    Higher excitation current needed to produce rated terminal voltage indicates a reduced magnetic coupling between rotor and stator — from increased air gap (bearing wear allowing rotor drop) or demagnetization of rotor field poles reducing flux per ampere.

  6. The slip of an induction motor is defined as and indicates:

    Answer: The difference between synchronous speed and rotor speed as a fraction of synchronous speed, and increases with increasing load

    Slip s = (Ns - Nr) / Ns, where Ns is synchronous speed and Nr is rotor speed. Slip is near zero at no load and increases to a few percent at full load for standard motors, as the rotor must lag synchronous speed to develop torque.