  1. NEC Article 800 governs communications circuits. These circuits are classified as:

    Answer: Communications circuits (limited energy)

    NEC Article 800 addresses communications circuits such as telephone and internet wiring, classified separately from Class 1, 2, and 3 circuits.

  2. Per NEC 338.10(B)(4), Type SE (service-entrance) cable used for interior branch circuit wiring must comply with which additional NEC article?

    Answer: Article 334

    NEC 338.10(B)(4)(a) requires that SE cable used for interior branch circuits comply with the installation requirements of NEC Article 334 (NM cable) except for ampacity.

  3. Which NEC section requires that all non-current-carrying metal parts of cord-and-plug-connected equipment be grounded?

    Answer: NEC 250.114

    NEC 250.114 lists the exposed non-current-carrying metal parts of cord-and-plug-connected equipment that must be grounded.

  4. Under NEC 410.116, recessed luminaires must be listed and marked for clearance from insulation. A Type IC fixture is designed to:

    Answer: Be in direct contact with insulation

    Type IC (Insulation Contact) recessed luminaires are listed for direct contact with thermal insulation, unlike non-IC types.

  5. According to NEC 445.13, the minimum conductor ampacity for generator output terminals and conductors within the generator enclosure must not be less than what percentage of the nameplate current rating?

    Answer: 115%

    NEC 445.13 requires generator output conductors and terminals to have an ampacity not less than 115% of the nameplate current rating.

  6. NEC 680.22(A) restricts the placement of receptacles near permanently installed swimming pools. What is the minimum distance from the pool wall for receptacles?

    Answer: 10 feet

    NEC 680.22(A)(1) requires receptacles to be located at least 6 feet from the inside walls of a permanently installed pool... wait — actually NEC 680.22(A)(1) sets 6 feet minimum, but 680.22(A)(4) allows receptacles between 6-10 feet only if GFCI-protected. The minimum is 6 feet.

  7. Per NEC 725.154, Class 2 and Class 3 cables installed in ducts, plenums, and other air-handling spaces must be listed as:

    Answer: CL2P or CL3P (plenum rated)

    NEC 725.154(A) requires CL2P or CL3P plenum-rated cables for installation in ducts and plenum air-handling spaces.