Electrical Code & Standards Flashcards
7 cards from real NECA practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Electrical Code & Standards flashcards as text
Under the NEC, what is the minimum burial depth for a residential branch circuit rated 120V GFCI-protected installed in rigid metal conduit (RMC)?
Answer: 6 inches
NEC Table 300.5 allows RMC burial at 6 inches for 120V GFCI-protected residential branch circuits.
Which NEC article governs the installation of electrical systems in hazardous (classified) locations using Zone equipment designation?
Answer: Article 505
NEC Article 505 covers Class I Zone 0, Zone 1, and Zone 2 hazardous locations using the IEC Zone system.
According to NEC 210.52, how many small-appliance branch circuits are required for kitchen countertop receptacles in a dwelling unit?
Answer: At least two 20-amp circuits
NEC 210.52(B)(1) requires at least two 20-amp small-appliance branch circuits for countertop receptacles in the kitchen.
What is the maximum distance from a water heater that a disconnect means must be located per NEC 422.31(B)?
Answer: In sight from the appliance
NEC 422.31(B) requires a disconnecting means within sight of the water heater unless it is lockable in the open position.
Per NEC 230.24(B), service-entrance conductors must maintain a minimum clearance of how many feet above a residential roof with a slope of 4 in 12 or greater?
Answer: 3 feet
NEC 230.24(B)(1) allows a 3-foot clearance above a roof with a slope of 4 in 12 or greater.
Which NFPA standard specifically addresses electrical safety requirements for employee workplaces and is closely referenced alongside the NEC by NECA members?
Answer: NFPA 70E
NFPA 70E covers electrical safety in the workplace and is the standard for arc flash and shock hazard protection for workers.
Under NEC 250.122, if a circuit breaker is increased in size for motor starting purposes, what must also be increased proportionally?
Answer: The equipment grounding conductor size
NEC 250.122(B) requires that when the overcurrent device is increased, the equipment grounding conductor must be proportionally increased in size.