Load Calculations & Branch Circuits Flashcards
7 cards from real NEC practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Load Calculations & Branch Circuits flashcards as text
Under the optional calculation method (NEC 220.82), what demand factor applies to the portion of the load over 10 kVA?
Answer: 40%
The optional method takes the first 10 kVA at 100% and the remainder at 40%.
In the optional method, the general lighting and small-appliance loads are combined with other loads and the first 10 kVA is taken at what percent?
Answer: 100%
The first 10 kVA of the combined general loads is taken at 100% in the optional calculation.
Using the optional method, which load is taken at the larger of 100% of A/C or 65% of central electric heating?
Answer: Heating/cooling
NEC 220.82(C) selects the largest among several heating/cooling scenarios, including 100% A/C or 65% of central heat.
What is the maximum number of 120-volt general-use receptacles considered acceptable on a 20-ampere residential circuit (no fixed limit, but rule of thumb)?
Answer: No NEC limit for dwellings
The NEC sets no numerical receptacle limit on general-purpose branch circuits in dwellings.
For non-dwelling occupancies, each general-use receptacle outlet is calculated at what VA per NEC 220.14(I)?
Answer: 180 VA
NEC 220.14(I) assigns 180 VA per single or multiple receptacle on one strap in non-dwelling occupancies.
A 1.5-ton residential A/C draws 24 A at 240 V. What VA is this for the optional calc?
Answer: 5760 VA
240 V x 24 A = 5760 VA.
Under the optional method, a household range nameplate of 12 kW is included at what value?
Answer: Nameplate 12 kW
The optional calculation uses the nameplate rating of appliances, so the full 12 kW is used in the combined load.