When calculating the load for a residential kitchen small appliance branch circuits, the NEC requires a minimum of how many 20-ampere circuits?
Answer: Two 20A circuits
NEC 210.11(C)(1) requires at least two 20-ampere small appliance branch circuits for receptacle outlets in kitchen, pantry, breakfast room, and dining room.
For a 240V, single-phase motor rated at 10 HP, what is the full-load current used for conductor sizing per NEC Table 430.250?
Answer: 50A
NEC Table 430.250 lists 50A as the full-load current for a 10 HP, 240V, single-phase motor.
Under NEC Article 220, what demand factor applies to the first 3,000 VA of general lighting load in a dwelling unit?
Answer: 100%
NEC Table 220.42 applies 100% demand factor to the first 3,000 VA of lighting load in a dwelling.
A commercial building has 40 receptacle outlets in an office area. Using the NEC standard load calculation, what load in VA is assigned per receptacle?
Answer: 180 VA
NEC 220.14(I) assigns 180 VA per receptacle outlet for calculating branch circuit and feeder loads in commercial occupancies.
When calculating a feeder load for a dwelling with a 12 kW electric range, what demand value does NEC Table 220.55 allow for a single range?
Answer: 8,000 VA
NEC Table 220.55 Column C permits 8 kW (8,000 VA) demand for a single household range rated over 8¾ kW through 12 kW.
For optional feeder/service calculations in dwellings per NEC 220.82, the first 10 kVA of all other loads after air conditioning is applied at what demand factor?
Answer: 100%
NEC 220.82(B) applies 100% demand factor to the first 10 kVA of all other loads in the optional calculation method.
A 120/240V, single-phase service feeds a dwelling. The calculated load is 28,800 VA. What is the minimum service ampacity required?
Answer: 150A
28,800 VA ÷ 240V = 120A; the next standard service size per NEC 230.79 is 150A, and residential minimum is 100A—but 120A requires 150A service.