What is the minimum size equipment grounding conductor (copper) for a circuit protected by a 100A overcurrent device per Table 250.122?
Answer: 8 AWG
NEC Table 250.122 specifies 8 AWG copper for a 100A overcurrent device.
A multiwire branch circuit must have a means to simultaneously disconnect which conductors at the panel?
Answer: All ungrounded conductors
NEC 210.4(B) requires simultaneous disconnection of all ungrounded conductors of a multiwire branch circuit.
What is the maximum overcurrent protection allowed for 14 AWG copper conductors under the small-conductor rule?
Answer: 15 A
NEC 240.4(D) limits 14 AWG copper to 15A overcurrent protection.
Where a panelboard is used as service equipment, the maximum number of main disconnects (the 'six-throw rule' before recent editions) was historically limited to how many?
Answer: 6
The traditional rule allowed up to six service disconnecting means; recent NEC editions require a single main in many cases.
What is the minimum working space depth (front) required for equipment 0-150V to ground with exposed live parts on one side, grounded on the other (Condition 1)?
Answer: 3 ft
NEC Table 110.26(A)(1) requires 3 ft of clear working space for Condition 1 at 0-150V.
Flexible cords and cables may NOT be used as a substitute for what?
Answer: Fixed wiring of a structure
NEC 400.12 prohibits using flexible cords as a substitute for the fixed wiring of a structure.
What is the maximum voltage drop recommended (not mandated) by the NEC for a branch circuit?
Answer: 3%
The NEC recommends a maximum 3% voltage drop on a branch circuit (5% total for feeder plus branch).