Commissioning and Troubleshooting Flashcards

7 cards from real NABCEP practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Commissioning and Troubleshooting flashcards as text
  1. A transformer-less string inverter produces an audible high-pitched noise during operation but otherwise functions normally. What is the most likely source?

    Answer: Switching frequency components from IGBT or MOSFET operation

    Transformerless inverters use high-frequency switching transistors that produce audible tones; this is normal but should be within manufacturer-specified noise limits.

  2. During commissioning of a commercial rooftop system, string voltages measured at the combiner box are 10% lower than calculated. All modules show normal Isc. What is the most likely cause?

    Answer: One module per string has been wired in reverse polarity, reducing net string voltage

    A single reverse-polarity module subtracts its voltage from the string total, causing a predictable voltage reduction without affecting Isc.

  3. What is the recommended sequence for powering up a newly commissioned grid-tied PV system for the first time?

    Answer: Verify all connections, close DC disconnect first, then AC breaker, observe inverter startup sequence

    Proper startup requires verifying connections, then energizing DC first so the inverter can detect PV voltage before connecting to the AC grid.

  4. A technician is troubleshooting a PV system where the inverter shows MPPT voltage significantly below the expected Vmpp range. Which fault is most consistent with this symptom?

    Answer: A string has developed an open circuit, reducing the number of series modules

    An open circuit in a string reduces the effective number of series modules, lowering the total MPPT voltage presented to the inverter.

  5. When verifying proper anti-islanding operation during commissioning, what standard test method is employed?

    Answer: Disconnect the utility feed and confirm the inverter shuts down within the required time per IEEE 1547

    Anti-islanding verification requires disconnecting the utility and confirming the inverter de-energizes within the time limits specified in IEEE 1547.

  6. A technician finds that the PV array's maximum system voltage, calculated at the site's record low temperature, exceeds the inverter's rated maximum input voltage. What is the proper corrective action?

    Answer: Remove modules from strings to reduce voltage below the inverter's maximum rating

    The only safe correction is to reduce the number of series modules so that Voc at minimum temperature does not exceed the inverter's maximum DC input voltage.

  7. During final commissioning walkthrough, the inspector notices PV conduit runs without visible expansion fittings on a 120-foot rooftop run. Why is this a concern?

    Answer: Thermal expansion of conduit without expansion fittings can stress connections and damage conduit

    Long conduit runs exposed to daily and seasonal temperature swings require expansion fittings to accommodate thermal expansion and prevent mechanical damage.