Backflow Prevention and Safety Flashcards

7 cards from real Master Plumber Exam practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Backflow Prevention and Safety flashcards as text
  1. An RPZ assembly relief valve is discharging water continuously during normal system operation. What is the most likely cause?

    Answer: Inlet pressure is too low

    If the first check valve fails to hold, the pressure in the zone drops below the inlet, causing the relief valve to open and discharge water continuously.

  2. Which backflow prevention method provides the highest level of protection for a potable water supply?

    Answer: Air gap

    An air gap is the only backflow prevention method that provides a complete physical separation between the supply and potential contaminant, making it the most reliable protection.

  3. Under ASSE 1013, what is the minimum relief valve opening differential pressure for a reduced pressure zone assembly?

    Answer: 2 psi

    ASSE 1013 requires the RPZ relief valve to open when the differential pressure across the first check drops to 2 psi or less, protecting the zone.

  4. A booster pump on a recirculating fire suppression system is connected to the potable water main. Which device is required at the connection?

    Answer: Double check detector assembly (DCDA)

    Fire suppression systems with pumps represent a potential backpressure hazard requiring a double check detector assembly to protect the potable supply.

  5. How often must testable backflow prevention assemblies typically be tested after initial installation under most US jurisdictions?

    Answer: Annually

    Most US jurisdictions require annual testing of all testable backflow prevention assemblies (RPZ, DCVA, PVB) by a certified tester.

  6. Which statement is TRUE about an atmospheric vacuum breaker (AVB)?

    Answer: It must be installed at least 6 inches above the highest downstream outlet

    An AVB must be installed at least 6 inches above the highest point of the downstream system to function correctly and prevent siphonage.

  7. What federal law mandates that public water systems protect their distribution systems from contamination caused by cross-connections?

    Answer: The Safe Drinking Water Act (SDWA)

    The Safe Drinking Water Act (SDWA) requires public water systems to implement cross-connection control programs to protect potable water quality.