When applying the optional calculation method for a dwelling unit, what is the minimum load in volt-amperes applied to the first 10 kVA of all other loads?
Answer: 100%
Under NEC 220.82, the first 10 kVA of all other loads is calculated at 100%, with the remainder at 40%.
A 240V, single-phase service feeds a 10 kW electric range. Using the standard calculation method, what demand load from NEC Table 220.55 applies for one range?
Answer: 8 kW
NEC Table 220.55, Column C specifies an 8 kW demand for a single household range rated up to 12 kW.
What is the minimum size service required for a single-family dwelling under NEC 230.79?
Answer: 100 amperes
NEC 230.79(C) requires a minimum 100-ampere, 3-wire service for a single-family dwelling.
When calculating feeder neutral load for a residential service, how is the unbalanced load between lines reduced per NEC 220.61?
Answer: The portion of neutral load above 200A may be reduced by 70%
NEC 220.61(B)(1) permits the neutral load above 200A to be multiplied by 70% for further reduction.
A commercial occupancy has 50,000 VA of receptacle load. What demand factor applies to the receptacle load above 10,000 VA per NEC Table 220.44?
Answer: 50%
NEC Table 220.44 allows the receptacle load exceeding 10,000 VA to be calculated at 50% demand.
Which NEC article governs services, including the number of service disconnects permitted?
Answer: NEC Article 230
NEC Article 230 covers services, including the rule that no more than six disconnecting means are permitted.
When sizing a service for a building with multiple HVAC units, how are the hermetic refrigerant motor-compressor loads treated per NEC 440.6?
Answer: At the rated-load current or branch-circuit selection current, whichever is greater
NEC 440.6 requires using the rated-load current or branch-circuit selection current (whichever is larger) as the load for each hermetic compressor.