Code, Theory, and Calculations Flashcards

7 cards from real Licensed Electrical Contractor practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Code, Theory, and Calculations flashcards as text
  1. According to NEC Article 310, what is the ampacity of a 12 AWG copper conductor with THHN insulation installed in a conduit with an ambient temperature of 30°C?

    Answer: 30 A

    A 12 AWG copper THHN conductor has a base ampacity of 30 A at 75°C column per NEC Table 310.15(B)(16), with no correction needed at 30°C ambient.

  2. When applying the NEC demand factor for household electric dryers in a multifamily building with 20 dryers, what demand factor applies per Table 220.54?

    Answer: 35%

    NEC Table 220.54 assigns a 35% demand factor for 20 household electric dryers in a multifamily dwelling.

  3. Kirchhoff's Voltage Law (KVL) states that the algebraic sum of all voltages around any closed loop equals:

    Answer: Zero

    KVL states that the sum of all voltage rises and drops around any closed loop is zero, reflecting conservation of energy.

  4. A 240 V single-phase motor draws 18 A at a power factor of 0.85. What is the true (real) power consumed?

    Answer: 3,672 W

    True power P = V × I × PF = 240 × 18 × 0.85 = 3,672 W.

  5. Under NEC 230.70, the service disconnecting means must be located:

    Answer: Inside the building as close as practicable to the point of service entry

    NEC 230.70 requires the service disconnect to be inside or outside the building nearest the point where the service conductors enter.

  6. In a parallel circuit, if one branch has a resistance of 10 Ω and another has 15 Ω, what is the total equivalent resistance?

    Answer: 6 Ω

    Parallel resistance: 1/Rt = 1/10 + 1/15 = 3/30 + 2/30 = 5/30, so Rt = 6 Ω.

  7. NEC Article 500 classifies hazardous locations. A Class I, Division 1 location is defined as one where:

    Answer: Flammable gases or vapors are present under normal operating conditions

    Class I, Division 1 locations are those where flammable gases or vapors exist in sufficient quantities under normal operating conditions to produce explosive mixtures.