  1. A 20-ampere branch circuit serves a small appliance circuit in a kitchen. What is the maximum load, in watts, allowed on this circuit at 120V using the 80% rule?

    Answer: 1,920 watts

    The 80% continuous load rule limits a 20A circuit at 120V to 20A × 0.80 × 120V = 1,920 watts.

  2. Per NEC Article 210, how many small appliance branch circuits are required for the kitchen countertop receptacle outlets in a dwelling unit?

    Answer: At least two 20-ampere circuits

    NEC 210.11(C)(1) requires at least two 20-ampere small appliance branch circuits for kitchen countertop receptacles.

  3. A branch circuit conductor must be sized so that voltage drop does not exceed what percentage for branch circuits per NEC recommendations?

    Answer: 3%

    The NEC recommends (informational note) that voltage drop on a branch circuit not exceed 3% for best performance.

  4. What is the minimum wire gauge (AWG) required for a 20-ampere, 120V branch circuit using copper conductors?

    Answer: 12 AWG

    NEC 240.4(D) requires 12 AWG copper conductors for circuits protected by 20-ampere overcurrent devices.

  5. A branch circuit supplies a 7.5 kVA, 240V single-phase motor load. What is the full-load current of this motor?

    Answer: 31.25 amperes

    I = kVA × 1000 / V = 7,500 / 240 = 31.25 amperes for a single-phase load.

  6. What NEC section governs the maximum number of outlets permitted on a branch circuit in a commercial occupancy?

    Answer: There is no NEC limit on number of outlets; load calculations govern

    The NEC does not set a maximum number of outlets per branch circuit; the total connected load determines the circuit size.

  7. For a branch circuit supplying a continuous load, the overcurrent protective device must be rated at no less than what percentage of the continuous load?

    Answer: 125%

    NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of the continuous load.