← All IEC Flashcard Decks

Transformers and Distribution Systems Flashcards

7 cards from real IEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Transformers and Distribution Systems flashcards as text
  1. According to NEC 450.3(B), for transformers rated 600V or less with a primary current of 9A or more, primary overcurrent protection must not exceed what percentage of rated primary current?

    Answer: 125%

    NEC 450.3(B) limits primary overcurrent protection to 125% of the transformer's rated primary current for this category of transformer.

  2. Per NEC 110.15, what color must be used to permanently identify the high-leg conductor in a 4-wire delta system?

    Answer: Orange

    NEC 110.15 requires the higher-voltage-to-ground (high leg) conductor in a 4-wire delta system to be identified with the color orange.

  3. Which secondary transformer connection creates a 'high leg' (wild leg) condition where one phase has a higher voltage to neutral than the other two phases?

    Answer: 4-wire Delta with center-tapped neutral

    A 4-wire delta system with one winding center-tapped for neutral creates a high leg with approximately 208V to neutral on a 240V delta system, while the other two phases measure only 120V to neutral.

  4. A transformer nameplate lists '5% impedance.' At full load, this means the internal voltage drop is what percentage of rated voltage?

    Answer: 5%

    Transformer impedance percentage directly represents the percentage of rated voltage that causes full-load current to flow through the transformer's internal impedance.

  5. According to NEC 450.41, transformer vault walls, roofs, and floors must have a minimum fire resistance rating of how many hours?

    Answer: 3 hours

    NEC 450.41 requires transformer vault construction to have a minimum 3-hour fire resistance rating to contain fire and protect the surrounding structure.

  6. What is the primary purpose of tap connections on a transformer's primary winding?

    Answer: To adjust the voltage ratio for variations in supply voltage

    Primary taps allow the turns ratio to be adjusted in small increments (typically 2.5% or 5%) to compensate for supply voltage that is higher or lower than the transformer's nominal rating.

  7. An open-delta (V-V) transformer bank can supply approximately what percentage of the three-phase capacity of a complete closed-delta bank using the same size transformers?

    Answer: 57.7%

    An open-delta bank delivers approximately 57.7% (= 1/√3) of the capacity of a full closed-delta bank because only two transformers carry the three-phase load.