A rater suspects that wind is affecting blower door readings. Which technique helps compensate for wind-induced pressure fluctuations?
Answer: Take multiple fan pressure readings and average them
Averaging multiple readings or using a data-logging manometer to record many samples over time compensates for short-term wind pressure fluctuations.
Which metric best represents the air tightness of a home independent of its volume?
Answer: ACH50
ACH50 (air changes per hour at 50 Pa) normalizes CFM50 by home volume, allowing meaningful comparisons between homes of different sizes.
During a duct blaster test, the technician notices pressure in the duct system won't reach 25 Pa even at maximum fan speed. What is the most likely cause?
Answer: There is a large unsealed duct opening or disconnected duct section
If the duct blaster cannot reach 25 Pa, it usually means there is an extremely large leak—such as a disconnected duct section or an unsealed chase—allowing air to escape faster than the fan can pressurize the system.
What is the formula for converting CFM50 to ACH50?
Answer: ACH50 = CFM50 × 60 / conditioned volume (ft³)
ACH50 = (CFM50 × 60 min/hr) ÷ conditioned volume in cubic feet, converting the per-minute flow to an hourly air change rate.
In a duct leakage test, what does a very low CFM25 out reading (near zero) with a relatively high CFM25 total reading suggest?
Answer: The duct system has significant leaks, all within the conditioned space
High total leakage with near-zero outside leakage means ducts are leaking significantly but all the leakage goes into conditioned space, not to unconditioned areas.
Which RESNET-recognized testing method allows duct leakage to be measured without pressurizing or depressurizing the entire duct system?
Answer: Delta Q method
The Delta Q method estimates duct leakage to outside by comparing house pressure with the air handler running versus off, without using a duct blaster.
A blower door test is performed on a home with a conditioned floor area of 2,500 ft² and 8 ft ceilings. CFM50 = 1,200. What is the ACH50?
Answer: 3.6 ACH50
Volume = 2,500 × 8 = 20,000 ft³; ACH50 = (1,200 × 60) / 20,000 = 72,000 / 20,000 = 3.6 ACH50.