  1. During inspection of a clean agent suppression system, the technician finds the agent cylinder weight is 5% below the listed weight. What action is required?

    Answer: Recharge or replace the cylinder immediately

    NFPA 2001 requires cylinders with agent loss exceeding 5% of net weight or a pressure loss of more than 10% to be recharged or replaced.

  2. What is a 'four-year internal inspection' requirement under NFPA 25, and to which system does it primarily apply?

    Answer: Internal pipe inspection of dry and preaction systems for microbiologically influenced corrosion

    NFPA 25 requires internal inspection of dry and preaction system piping every 4 years to check for corrosion, scale, and microbiologically influenced corrosion (MIC).

  3. A technician performing a semi-annual fire pump test records a churn (no-flow) pressure reading. What is the acceptable variance from the original acceptance test data?

    Answer: Up to 10% variation is acceptable

    NFPA 25 allows up to a 10% decrease in pump pressure from the original acceptance test before requiring corrective action.

  4. When is a 'witnessed test' by the AHJ typically required for a fire protection system?

    Answer: During installation acceptance testing and after major modifications

    The AHJ typically witnesses acceptance tests after new installation or major modifications to verify the system meets code requirements before occupancy.

  5. A technician inspects a fire department connection (FDC) and finds the swivel coupling is seized and will not rotate. What is the correct action?

    Answer: Tag the FDC out of service and arrange for repair

    A seized FDC swivel prevents firefighters from quickly connecting their hose, making it a critical deficiency requiring immediate repair.

  6. Under NFPA 72, which test is used to verify that a manual pull station sends a correct alarm signal to the fire alarm control unit?

    Answer: Functional test

    A functional test of a manual pull station requires actually operating the device to confirm it transmits a valid alarm signal to the control unit.

  7. When a fire sprinkler system is taken out of service for more than 10 hours in a 24-hour period, what must the technician ensure is in place?

    Answer: An approved fire watch and notification to the AHJ and insurance carrier

    NFPA 25 and most codes require a fire watch and notification to the AHJ and insurance carrier when a system is impaired for more than 10 hours in a 24-hour period.