โ† All F60 Flashcard Decks

Fire Guard Responsibilities Flashcards

6 cards from real F60 practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 Fire Guard Responsibilities flashcards as text
  1. A Fire Guard is conducting a fire watch for a torch operation on a construction site. After the torch work is completed for the day, what is the MINIMUM amount of time the Fire Guard must continue to monitor the area?

    Answer: 30 minutes

    According to FDNY regulations and standard hot work safety procedures, the fire watch must continue for at least 30 minutes after the completion of torch operations to detect and extinguish any smoldering fires.

  2. During a pre-work inspection, a Fire Guard notices combustible materials located 20 feet away from the designated torch operation area. The materials cannot be moved. Which of the following is the most appropriate action for the Fire Guard to take?

    Answer: Ensure the combustible materials are shielded with fire-resistant guards or curtains before allowing work to begin.

    FDNY regulations state that torch operations involving cutting or welding must be conducted at least 35 feet from combustible materials. If combustibles are closer and cannot be moved, they must be protected with appropriate shielding, such as fire-resistant guards or curtains, before work can commence.

  3. A torch operator is working on a rooftop, and the F60 Fire Guard needs to leave the area for a short time. What is the correct procedure?

    Answer: Stop all torch operations until a qualified replacement Fire Guard is present.

    The fire watch must be continuous. If a Fire Guard must leave their post for any reason, all hot work operations must cease until a qualified replacement is assigned and present to continue the fire watch.

  4. Which of the following is a primary responsibility of an F60 Fire Guard BEFORE torch operations begin?

    Answer: Ensuring the hot work permit is signed and available for inspection.

    The Fire Guard is responsible for verifying that all safety conditions are met before work starts. This includes ensuring a hot work authorization or permit has been properly issued by a responsible person and is available on-site for inspection by the Fire Department.

  5. While performing a fire watch, you see a small fire ignite from a stray spark. You have a portable fire extinguisher readily available. What should be your immediate course of action?

    Answer: Attempt to extinguish the fire only if it is within the capacity of your extinguisher.

    A Fire Guard's training includes using a portable fire extinguisher. If a fire starts, they should attempt to extinguish it, but only if the fire is small enough to be handled by the available equipment. If it is beyond the capacity of the extinguisher, they should sound the alarm immediately.

  6. An F60 Fire Guard is NOT authorized to perform fire watch duties under which of the following circumstances?

    Answer: In a building where the fire alarm system is out of service for more than four hours, and no torch work is occurring.

    The F60 Certificate of Fitness is specifically for fire watch during torch operations. A fire watch for an impairment of a fire protection system (like an alarm or sprinkler system being out of service) requires a different Certificate of Fitness, the F-01.