  1. For a standard torch operation at a construction site, what is the MINIMUM rating for a portable fire extinguisher that must be readily accessible?

    Answer: 2-A:20-B:C

    The FDNY requires at least one portable fire extinguisher with a minimum rating of 2-A:20-B:C to be readily accessible within 30 feet of where hot work is performed. A higher rating is required for specific operations like torch-applied roofing.

  2. A Fire Guard is overseeing a torch-applied roofing system operation. Which of the following fire extinguishers is required as a MINIMUM for this specific task?

    Answer: One with a 3-A:40-B:C rating

    Due to the increased hazards associated with torch-applied roofing, the FDNY mandates a more powerful fire extinguisher. A multi-purpose portable fire extinguisher with at least a 3-A:40-B:C rating is required for these specific operations.

  3. If a portable fire extinguisher is used to put out a small fire during a torch operation, what is the correct procedure before work can continue?

    Answer: Stop all work until a fully charged replacement extinguisher is in place.

    The FDNY F60 study material explicitly states that in the event a fire extinguisher has been discharged, a fully charged replacement is required before hot work can resume. This ensures that fire protection is maintained.

  4. A Fire Guard must ensure a portable fire extinguisher is readily accessible to the hot work area. What is the MAXIMUM allowable travel distance from the operation to the extinguisher?

    Answer: 30 feet

    According to FDNY regulations for F60 Fire Guards, a portable fire extinguisher must be readily accessible within a 30-foot travel distance of the location where hot work is being performed and where the fire guards are positioned.

  5. During a daily pre-work inspection, an F60 Fire Guard examines the portable fire extinguisher tag. Which feature, according to FDNY rules, helps verify the tag is authentic and not fraudulent?

    Answer: A hologram that displays an array of colors.

    To combat fraudulent servicing, the FDNY issues special tags with security features. These include a specific shape, size, color, and a hologram on the front to prevent fraudulent reproduction.

  6. Which of the following statements is TRUE regarding the training for using a fire extinguisher for an F60 Fire Guard?

    Answer: All persons conducting hot work or fire watch must be trained in the use of portable fire extinguishers.

    The FDNY requires that all individuals conducting hot work operations or performing the fire watch must be trained in the use of portable fire extinguishers and be capable of extinguishing small, incipient-stage fires.