Refrigeration and Air Conditioning Regulations Flashcards

7 cards from real EPA practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Refrigeration and Air Conditioning Regulations flashcards as text
  1. A technician recovers R-22 from a high-pressure appliance with 250 lb of refrigerant, built after November 15, 1993, using recovery equipment made after that date. What level of evacuation is required?

    Answer: 10 inches Hg vacuum

    HCFC-22 appliances with 200 lb or more of refrigerant must be evacuated to 10 inches Hg vacuum.

  2. What is the required evacuation level for an HCFC-22 appliance containing less than 200 lb of refrigerant when using recovery equipment made after November 15, 1993?

    Answer: 0 inches Hg

    HCFC-22 appliances with less than 200 lb of refrigerant must be evacuated to 0 inches Hg.

  3. Low-pressure appliances serviced with recovery equipment made after November 15, 1993 must be evacuated to what level?

    Answer: 25 mm Hg absolute

    Low-pressure appliances must be evacuated to 25 mm Hg absolute, which is about 29 inches Hg vacuum.

  4. A high-pressure appliance has a leak that makes it impossible to reach the required vacuum. What is the minimum required evacuation level?

    Answer: Atmospheric pressure (0 psig)

    If leaks make the required vacuum impossible to reach, the technician must still evacuate to atmospheric pressure.

  5. A small appliance has an inoperative compressor. Using recovery equipment made after November 15, 1993, what percentage of the refrigerant must be recovered?

    Answer: 80%

    Small appliances with a non-working compressor require 80% recovery, or evacuation to 4 inches Hg vacuum.

  6. What is the maximum refrigerant charge for an appliance on which system-dependent (passive) recovery equipment may be used?

    Answer: 15 lb

    System-dependent recovery equipment may only be used on appliances containing 15 lb of refrigerant or less.

  7. Which of these is an alternative to the 90% recovery requirement for a small appliance with a working compressor?

    Answer: Evacuating to 4 inches Hg vacuum

    Small-appliance recovery is met by either the required percentage or evacuation to 4 inches Hg vacuum.