  1. What is the maximum amount a refillable refrigerant cylinder should be filled?

    Answer: 80% of its liquid capacity

    Leaving 20% vapor space allows for liquid expansion as temperature rises.

  2. What colors identify a DOT-approved refrigerant recovery cylinder?

    Answer: Gray body with yellow top

    Recovery cylinders are gray with yellow shoulders or tops.

  3. How often must refillable refrigerant recovery cylinders be hydrostatically tested?

    Answer: Every 5 years

    DOT requires refillable cylinders to be hydrostatically retested every five years, with the date stamped on the cylinder.

  4. Before disposing of a disposable (non-refillable) refrigerant cylinder, the technician should:

    Answer: Recover remaining refrigerant to 0 psig and render the cylinder useless

    Empty disposable cylinders are recovered to 0 psig, then punctured or marked empty before recycling as scrap metal.

  5. What information must accompany a cylinder of used refrigerant being shipped to a reclaimer?

    Answer: DOT classification tag and label showing refrigerant type and quantity

    Shipped cylinders need DOT labeling and a tag identifying the refrigerant type and amount.

  6. Why should refrigerant cylinders never be heated with an open flame or stored above 125°F?

    Answer: Pressure can rise enough to rupture the cylinder

    Heat raises cylinder pressure rapidly and can cause a rupture or explosion.

  7. What gas should be used with a pressure regulator to pressurize a system for leak testing?

    Answer: Dry nitrogen

    Dry nitrogen is inert and safe, while oxygen or air can explode when mixed with compressor oil under pressure.