Paralleling and Switchgear Controls Flashcards

7 cards from real EGSA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Paralleling and Switchgear Controls flashcards as text
  1. What is the purpose of reactive droop compensation in an automatic voltage regulator (AVR) when generators are paralleled?

    Answer: To provide a drooping VAR-vs-voltage characteristic that promotes stable reactive load sharing

    Reactive droop (cross-current compensation) intentionally reduces AVR output as reactive output increases, creating a drooping characteristic that stabilizes reactive load division between paralleled machines.

  2. A transfer scheme described as 'open transition' with 'in-phase monitoring' will:

    Answer: Open the normal source before closing the alternate source, but only when both sources are in phase

    In-phase open transition waits for the natural voltage crossover point where both sources are momentarily in phase, then opens the normal source and immediately closes the alternate source, minimizing transfer transients.

  3. What condition is indicated when the frequency difference between paralleled generators results in a 'beat' frequency on the bus voltage waveform?

    Answer: The generators have a slip frequency and are not yet fully synchronized

    A beat frequency (amplitude modulation of the bus voltage) indicates a frequency difference (slip) between two generators that are running at slightly different speeds.

  4. In switchgear applications, what is the significance of an 'electrically operated' vs. a 'manually operated' circuit breaker?

    Answer: Electrically operated breakers can be controlled remotely via SCADA or relay outputs without physical operator presence

    Electrically operated breakers have motor-charged spring mechanisms and solenoid trip/close coils, enabling remote control, automatic relay tripping, and SCADA integration without a local operator.

  5. Which device function would be used to detect a generator operating as a motor (prime mover failure) in a paralleled system?

    Answer: ANSI 32 – Directional power (reverse power) relay

    The ANSI 32 reverse power relay detects when real power flow reverses (generator motoring) due to prime mover failure, and trips the generator breaker to protect the prime mover.

  6. What does the term 'kW load sharing error' refer to in a paralleled generator control system?

    Answer: The deviation of each generator's real power output from its proportional share of total system load

    kW load sharing error is the difference between a generator's actual real power output and its target proportional share; load share controllers minimize this error by adjusting governor speed references.

  7. A synchronizing panel's 'permissive close' output will be de-asserted (blocked) if which condition exists?

    Answer: Voltage difference between generator and bus exceeds the set window (e.g., ±5%)

    If the voltage magnitude difference between the incoming generator and the bus exceeds the synchronizer's voltage window setting, the permissive close output is blocked to prevent damaging inrush currents.