Automatic Transfer Switch Function Flashcards
7 cards from real EGSA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Automatic Transfer Switch Function flashcards as text
What type of ATS performs a 'make-before-break' switching sequence?
Answer: Closed-transition ATS
A closed-transition ATS briefly parallels both sources during transfer, making the connection to the new source before breaking from the old source to achieve a seamless transfer.
Which NFPA 110 Type designation requires the ATS to transfer load within 10 seconds?
Answer: Type 10
NFPA 110 Type 10 specifies that the alternate power source must supply power to the load within 10 seconds of normal source failure.
When an ATS is described as 'switched neutral,' it means the neutral is:
Answer: Transferred simultaneously with the phase conductors
A switched neutral (four-pole) ATS transfers the neutral conductor along with the phase conductors, required for separately derived systems where each source has its own neutral-ground bond.
What is the function of a 'load shed' output on an ATS controller?
Answer: To signal non-critical loads to disconnect when the generator is supplying power
The load shed output signals load management panels to disconnect non-essential loads, preventing generator overload when critical and non-critical loads share the same emergency distribution system.
A 'programmed transition' ATS differs from a standard open-transition ATS because it:
Answer: Waits a fixed time in neutral to allow motors to de-energize before reconnecting
A programmed transition ATS adds a fixed neutral dwell time between opening one source and closing the other, reducing voltage transients caused by residual motor flux.
What is the significance of the ATS 'withstand and closing rating' (WCR)?
Answer: The ATS's ability to remain closed and then close onto available fault current without damage
WCR defines the maximum available fault current at which the ATS can remain closed (withstand) and subsequently close (closing rating) without damage, ensuring system protection coordination.
Which of the following best describes 'voltage window' settings in an ATS controller?
Answer: Upper and lower voltage thresholds that define acceptable source quality for load connection
Voltage window settings define the acceptable voltage band (typically 90–110% of nominal) within which a source is considered 'acceptable' for load connection or retransfer.