What is the maximum number of 90-degree bends permitted in a single run of rigid metal conduit (RMC) between pull points?
Answer: Four 90-degree bends
NEC 358.26 limits the total bends to 360 degrees (equivalent to four 90-degree bends) between pull points in EMT and RMC runs.
Which wiring method is specifically listed for use in hazardous (classified) locations Class I, Division 1?
Answer: Rigid metal conduit (RMC)
Rigid metal conduit (RMC) is one of the approved wiring methods for Class I, Division 1 hazardous locations per NEC Article 501.
When installing PVC conduit underground, what is the minimum cover required for a branch circuit rated 120V or less under a residential driveway?
Answer: 18 inches
NEC Table 300.5 requires 18 inches of cover for PVC conduit under residential driveways for circuits 120V or less.
What is the minimum radius for a field bend in 2-inch RMC?
Answer: 9.5 inches
NEC Table 344.24 specifies a minimum bend radius of 9.5 inches for 2-inch RMC to prevent conductor damage.
Type UF cable differs from Type NM cable primarily because UF cable is:
Answer: Suitable for direct burial in the earth
Type UF (Underground Feeder) cable has a moisture-resistant, sunlight-resistant jacket approved for direct burial per NEC 340.10.
Which of the following conduit types is NOT permitted to be used as an equipment grounding conductor?
Answer: Rigid polyvinyl chloride conduit (PVC)
PVC conduit is a non-metallic raceway and cannot serve as an equipment grounding conductor; a separate EGC must be installed.
When using flexible metal conduit (FMC) for a motor connection, what is the maximum length permitted without an additional equipment grounding conductor?
Answer: 6 feet
NEC 350.60 allows FMC up to 6 feet to serve as the EGC provided it meets the listed conditions, including a minimum trade size of ½ inch.