Under NEC Article 230, what is the maximum number of service disconnects permitted for a single commercial occupancy?
Answer: 6
NEC 230.71 allows a maximum of six service disconnects for a single commercial occupancy grouped in one location.
NEC 210.19(A) requires that branch circuit conductors have an ampacity of at least what percentage of the continuous load they serve?
Answer: 125%
Conductors must be sized at 125% of the continuous load to account for heat buildup under sustained operation.
According to NEC 450.13, a dry-type transformer rated 112.5 kVA or less must have a minimum clearance of how many inches from combustible material?
Answer: 12 inches
NEC 450.13(A) requires at least 12 inches of separation between a dry-type transformer and combustible material unless the transformer is separated by a fire-resistant, heat-insulating barrier.
NEC 700.12 requires emergency system sources to supply full load within how many seconds of normal power failure?
Answer: 10 seconds
Emergency systems must restore power within 10 seconds of normal source failure per NEC 700.12.
Under NEC 404.2(C), a switch controlling a lighting outlet in a bathroom of a commercial occupancy must be located where?
Answer: Inside the bathroom, away from the tub or shower
NEC 404.2(C) permits switches inside bathrooms if they are not within reach of a tub or shower.
NEC 517.13 requires that patient care areas in healthcare facilities have what special grounding provision for receptacles and fixed equipment?
Answer: An insulated equipment grounding conductor in addition to the metallic raceway path
NEC 517.13 mandates a redundant grounding path: both the metal raceway and an insulated EGC must be present to ensure continuity in patient care areas.
According to NEC 225.30, a commercial building may have a maximum of how many feeder or branch circuit supplies from outside the building?
Answer: One
NEC 225.30 limits outside feeder or branch circuit supplies to one per building or structure, with specific listed exceptions.