Health Care Facilities Flashcards
7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Health Care Facilities flashcards as text
In a patient care area, what is the maximum allowable voltage between any two accessible conductive surfaces in a general care area?
Answer: 50 mV
NEC 517.13 requires that the voltage between any two accessible conductive surfaces in a general care area not exceed 50 mV (millivolts).
Which NEC article specifically covers the electrical requirements for health care facilities?
Answer: Article 517
NEC Article 517 covers electrical wiring and equipment in health care facilities including hospitals, nursing homes, and clinics.
What is the minimum size equipment grounding conductor required for a branch circuit in a critical care area?
Answer: 10 AWG copper
NEC 517.13(A) requires an insulated copper equipment grounding conductor, minimum 10 AWG, for branch circuits serving patient care areas in critical care spaces.
In a Type 1 essential electrical system, the automatic transfer to generator power must occur within how many seconds?
Answer: 10 seconds
NEC 517.30 and NFPA 99 require that the life safety and critical branches of a Type 1 EES transfer to alternate power within 10 seconds of normal power failure.
A wet procedure location in a health care facility is defined as one where:
Answer: Liquids are intentionally used as part of the procedure
NEC 517.2 defines a wet procedure location as one in which a procedure is performed and water or conductive liquids are intentionally used or administered.
What type of receptacles are required in critical care patient bed locations?
Answer: Hospital-grade receptacles
NEC 517.18(B) requires hospital-grade receptacles at patient bed locations in critical care areas to ensure reliable connections for life-supporting equipment.
Which branch of the essential electrical system in a hospital must power the fire alarm system?
Answer: Life safety branch
NEC 517.32 specifies that the fire alarm system must be connected to the life safety branch of the essential electrical system.