Hazardous (Classified) Locations Flashcards
7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Hazardous (Classified) Locations flashcards as text
Flexible connections in Class I, Division 1 locations must use which type of flexible fitting?
Answer: Listed flexible fittings approved for the location
Flexible connections in Class I, Division 1 locations must use listed flexible fittings specifically approved for use in that classified location.
In a Class II, Division 1 location, motors must be of which type?
Answer: Dust-ignition-proof
Motors in Class II, Division 1 locations must be dust-ignition-proof to prevent ignition of combustible dust accumulations.
What is the maximum distance from a Class I, Division 1 or 2 enclosure that a conduit seal must be installed?
Answer: 18 inches
NEC Section 501.15 requires conduit seals to be installed within 18 inches of a Class I, Division 1 or 2 enclosure.
Which Group classification covers acetylene in Class I hazardous locations?
Answer: Group A
Acetylene is classified in Group A, which represents the most sensitive and dangerous gas group in Class I locations.
Intrinsically safe equipment is defined as equipment that:
Answer: Cannot produce sparks or thermal effects capable of igniting a hazardous mixture
Intrinsically safe equipment is incapable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of a specific hazardous atmospheric mixture.
A grain elevator storage area with combustible grain dust would be classified under which Class and Group?
Answer: Class II, Group G
Grain dust is classified as Class II, Group G, which covers agricultural dusts including grain, flour, and starch.
In a Class I hazardous location, which type of luminaire (light fixture) is required in Division 1 areas?
Answer: Explosion-proof luminaire listed for Class I, Division 1
Luminaires in Class I, Division 1 locations must be explosion-proof and specifically listed for Class I, Division 1 use.