Commercial Service Load Calculations Flashcards
7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Commercial Service Load Calculations flashcards as text
What is the unit lighting load per square foot for office occupancies per NEC Table 220.12?
Answer: 3.5 VA/sq ft
NEC Table 220.12 specifies 3.5 VA per square foot as the unit lighting load for office occupancies.
Per NEC 220.44, what demand factor applies to the portion of non-dwelling receptacle load that exceeds 10 kVA?
Answer: 50%
NEC 220.44 permits a 50% demand factor on non-dwelling receptacle loads exceeding the first 10 kVA.
What is the unit lighting load per square foot for a mercantile (retail store) occupancy per NEC Table 220.12?
Answer: 3.0 VA/sq ft
NEC Table 220.12 lists 3 VA per square foot as the unit lighting load for mercantile occupancies.
How many volt-amperes is assigned to each duplex receptacle outlet in a non-dwelling commercial occupancy per NEC 220.14(I)?
Answer: 180 VA
NEC 220.14(I) assigns 180 VA to each single or multiple receptacle on one yoke in non-dwelling occupancies.
For 'all other' commercial occupancies per NEC Table 220.42, what demand factor applies to lighting loads exceeding 50,000 VA?
Answer: 50%
NEC Table 220.42 allows a 50% demand factor on lighting loads over 50,000 VA for most commercial occupancies.
Which NEC article primarily governs branch circuit, feeder, and service load calculations for commercial buildings?
Answer: Article 220
NEC Article 220 specifically covers load calculation methods for branch circuits, feeders, and services.
A 25,000 sq ft office building is being permitted. What is the minimum general lighting load before applying any demand factors?
Answer: 87,500 VA
Office occupancies use 3.5 VA/sq ft per NEC Table 220.12, so 25,000 ร 3.5 = 87,500 VA.