Pathways and Spaces Flashcards
7 cards from real DCI practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Pathways and Spaces flashcards as text
What is the minimum clearance required above a suspended ceiling used as a plenum return air pathway when installing cable trays?
Answer: 12 inches
A minimum of 12 inches of clearance is typically required above suspended ceilings used as plenum return air pathways to allow for proper airflow and cable management.
Which standard governs the installation of cable trays in the United States?
Answer: NEMA VE-1
NEMA VE-1 is the standard that specifically governs the design and installation of metal cable trays in the United States.
A conduit body that makes a 90-degree change in direction is commonly called a(n):
Answer: LB fitting
An LB fitting (conduit body) is used to make a 90-degree change of direction in a conduit run while also providing a pull point.
When pulling cable through a conduit, what is the maximum recommended fill ratio for a single cable?
Answer: 53%
For a single cable in a conduit, the maximum recommended fill ratio is 53% of the conduit's cross-sectional area per NEC guidelines.
In a data center, a hot aisle/cold aisle layout primarily affects which pathway and spaces consideration?
Answer: Underfloor cable routing and airflow management
Hot aisle/cold aisle layouts directly impact underfloor cable routing and airflow management, as cables must be routed to avoid blocking cold air supply tiles.
What term describes a pathway that runs horizontally between the telecommunications room and the work area outlets?
Answer: Horizontal pathway
A horizontal pathway runs horizontally from the telecommunications room (TR) to the work area telecommunications outlet/connectors.
Which of the following is NOT a typical type of surface raceway used for horizontal cable distribution?
Answer: Cable tray ladder
A cable tray ladder is an overhead pathway system, not a surface raceway; baseboard, multiduct, and cellular floor systems are all types of surface raceways.