What is the primary purpose of a thermocouple in process instrumentation?
Answer: Measure temperature by generating a voltage
A thermocouple generates a small voltage proportional to the temperature difference between its hot and cold junctions, which is used to infer temperature.
A control valve fails to respond to the positioner signal. Which component should be checked first?
Answer: The instrument air supply pressure
Insufficient instrument air supply pressure is the most common reason a pneumatic control valve fails to respond to its positioner signal.
What does the term 'dead band' refer to in a control instrument?
Answer: The range of input change that produces no output change
Dead band is the range over which an input signal can change without causing a corresponding change in output, and it causes hysteresis in the control loop.
Which maintenance strategy involves replacing components based on their predicted service life before failure occurs?
Answer: Preventive maintenance
Preventive maintenance involves scheduled replacement or servicing of equipment at predetermined intervals to prevent unexpected failures.
A pressure transmitter reads higher than expected. After zeroing, the reading is still off-scale. What is the most likely cause?
Answer: Plugged impulse line
A plugged impulse line traps pressure and prevents the transmitter from sensing actual process pressure, causing an erroneously high or stuck reading.
What is the function of a seal pot in an impulse line system?
Answer: Maintain equal liquid head on both impulse lines for accurate DP measurement
Seal pots maintain equal and constant liquid levels in both high- and low-side impulse lines, ensuring the hydrostatic head cancels out for accurate differential pressure measurement.
When calibrating a 4–20 mA transmitter, what output signal corresponds to 0% of the measurement range?
Answer: 4 mA
In a 4–20 mA loop, 4 mA represents 0% of the measurement span, and 20 mA represents 100%, with the 4 mA offset used to detect open-circuit faults.