Sanitary Drainage Systems Flashcards

7 cards from real CPD practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Sanitary Drainage Systems flashcards as text
  1. A stack serving more than 10 branch intervals must be provided with a:

    Answer: Yoke vent at every fifth interval

    The IPC requires yoke vents (relief vents) at every fifth interval when a drainage stack serves more than 10 branch intervals to relieve pressure fluctuations.

  2. Which material is generally NOT approved for underground sanitary drain piping inside a building per the IPC?

    Answer: Threaded galvanized steel

    Threaded galvanized steel is not approved for underground sanitary drainage because it corrodes rapidly when buried and exposed to wastewater.

  3. In sanitary drainage design, what is a 'branch interval'?

    Answer: A vertical measurement of at least 8 feet along a drainage stack

    A branch interval is a vertical measurement of not less than 8 feet within a stack, representing the space between horizontal branch connections.

  4. Which of the following scenarios requires an indirect waste connection rather than a direct drain connection?

    Answer: A commercial dishwasher in a restaurant kitchen

    Commercial dishwashers must discharge through an indirect waste connection with an air gap to prevent contamination of the potable or sanitary system by backflow.

  5. When a sanitary drain must pass under a footing, the minimum clearance between the top of the pipe and the bottom of the footing is:

    Answer: No clearance required if pipe is in a sleeve

    When a pipe passes under a footing, IPC allows it if properly sleeved or protected such that the footing load is not transferred to the pipe.

  6. What is the maximum distance a trap arm may extend horizontally from the trap weir to the vent for a 2-inch drain?

    Answer: 6 feet

    Per IPC Table 909.1, a 2-inch trap arm has a maximum developed length of 6 feet from the trap weir to the vent.

  7. Which venting method uses a fitting designed with an internal air-admittance mechanism to vent individual fixtures?

    Answer: Air admittance valve (AAV)

    An air admittance valve (AAV) is a mechanical vent device that opens under negative pressure to admit air and closes to prevent sewer gas escape.