  1. Under NEC Article 230, what is the maximum number of service disconnects permitted for a single-occupancy building?

    Answer: Six

    NEC 230.71 allows a maximum of six disconnecting means for a single set of service-entrance conductors.

  2. Which NEC article governs the installation of transformers with a primary voltage over 600V?

    Answer: Article 450

    NEC Article 450 covers transformers and transformer vaults, including those rated over 600V.

  3. What does the NEC require for overcurrent protection of a 480V, 3-phase, 100 kVA transformer with a secondary of 208Y/120V?

    Answer: Primary protection set at 125% of rated current satisfies the NEC for most cases

    Per NEC 450.3, primary overcurrent protection set no more than 125% of rated primary current is the standard requirement for most transformers.

  4. NEC 310.15 ampacity tables are based on an ambient temperature of how many degrees Celsius?

    Answer: 30°C

    NEC ampacity tables in 310.15 are based on a 30°C (86°F) ambient temperature unless otherwise noted.

  5. According to NEC 250.122, if a feeder circuit's overcurrent device is increased in size to handle a larger load, what must also be increased?

    Answer: The equipment grounding conductor

    NEC 250.122(B) requires the equipment grounding conductor to be proportionally increased when the OCPD is upsized.

  6. Under NFPA 70E, what arc flash PPE category requires a minimum arc rating of 40 cal/cm²?

    Answer: Category 4

    NFPA 70E Table 130.5(G) assigns PPE Category 4 a minimum arc rating of 40 cal/cm².

  7. Which NEC section defines the requirements for working clearances in front of electrical equipment operating at 600V or less?

    Answer: NEC 110.26

    NEC 110.26 specifies minimum working clearances, dedicated space, and headroom requirements for equipment up to 1000V.