Detection and Alarm Systems Flashcards
7 cards from real CFPS practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Detection and Alarm Systems flashcards as text
Under NFPA 72, which wiring class allows a single open or ground fault to render an entire circuit inoperable?
Answer: Class B
Class B circuits are not supervised for opens or shorts at every point, so a single fault can disable the entire circuit.
A projected beam smoke detector measures which property to detect smoke?
Answer: Reduction in infrared light intensity across a path
Projected beam detectors measure attenuation of a light beam transmitted across a protected area; smoke reduces the received signal.
NFPA 72 defines the Temporal-3 evacuation signal as:
Answer: Three short pulses, pause, repeated
Temporal Pattern 3 is 0.5-s ON, 0.5-s OFF, 0.5-s ON, 0.5-s OFF, 0.5-s ON, then 1.5-s OFF, repeated continuously.
Which initiating device would be MOST appropriate to detect a slow smoldering fire in a large warehouse?
Answer: Air-sampling (aspirating) smoke detector
Air-sampling detectors actively draw air through a pipe network and can detect very low smoke concentrations produced by early-stage smoldering fires.
What is the purpose of a duct smoke detector installed in an HVAC return-air duct?
Answer: To prevent smoke from being recirculated through the HVAC system
Duct detectors shut down the air-handling unit and close dampers to prevent smoke from spreading through the duct system to other areas.
According to NFPA 72, a supervisory signal from a sprinkler control valve indicates:
Answer: An abnormal condition requiring attention but not immediate evacuation
Supervisory signals indicate off-normal conditions (such as a closed valve) that need correction but do not by themselves require evacuation.
A flame detector that responds to radiant energy in the 4.3-micron CO₂ absorption band is classified as:
Answer: Infrared (IR) detector
The 4.3-micron band is a characteristic infrared emission of hot CO₂ produced in hydrocarbon flames, making this an IR flame detector.