Life Safety & Emergency Systems Flashcards

7 cards from real CFI practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Life Safety & Emergency Systems flashcards as text
  1. During a fire inspection, an inspector finds that a fire door is held open with a rope tied to the door hardware. What is the correct action?

    Answer: Issue a violation and require immediate correction

    Fire doors must not be held open by any unapproved means; the inspector must issue a violation and require immediate removal of the obstruction.

  2. NFPA 101 requires that exit signs be illuminated at all times the building is occupied. What is the minimum illumination level on the face of the sign?

    Answer: 1 foot-candle

    NFPA 101 requires exit sign faces to be illuminated to a minimum of 1 foot-candle under normal conditions.

  3. A building inspector observes that a stairwell door self-closes but does not latch. This condition is a code violation primarily because:

    Answer: The rated assembly requires the door to latch to maintain its fire-resistance rating

    A fire-rated door assembly must latch to form a complete barrier; an unlatched door cannot maintain the rated resistance to fire and smoke.

  4. Under NFPA 13, what is the minimum distance a standard spray sprinkler head must be installed from a wall?

    Answer: 4 inches

    NFPA 13 requires standard spray sprinklers to be positioned a minimum of 4 inches from any wall to ensure effective water distribution.

  5. An emergency generator supplying egress lighting must reach full operation within how many seconds of normal power failure under NFPA 110?

    Answer: 10 seconds

    NFPA 110 requires Level 1 emergency power supply systems (EPSS) to restore power within 10 seconds of normal power failure.

  6. Which occupancy classification under NFPA 101 includes nightclubs and theaters where occupants are unfamiliar with the exits?

    Answer: Assembly

    Assembly occupancies include nightclubs, theaters, and similar spaces where large numbers of people who may be unfamiliar with the building gather.

  7. A fire inspector notes that portable fire extinguishers in an office building have not been inspected. According to NFPA 10, extinguishers must receive a physical inspection at what minimum frequency?

    Answer: Monthly

    NFPA 10 requires that portable fire extinguishers receive a quick visual inspection at least monthly to confirm they are in their designated location and ready for use.