Refrigerant Identification & Testing Flashcards
7 cards from real CFC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Refrigerant Identification & Testing flashcards as text
What is the ASHRAE numerical designation for the refrigerant formerly known by the trade name Freon-12?
Answer: R-12
Freon-12 is designated R-12 under the ASHRAE refrigerant numbering system, a fully halogenated CFC that was phased out under the Montreal Protocol.
What is the standard AHRI cylinder color for R-134a refrigerant?
Answer: Sky blue
R-134a cylinders are painted sky blue (light blue) per AHRI cylinder color-coding standards, distinguishing it from R-22 (light green) and R-12 (white).
When using a refrigerant identifier and receiving a 'FAIL - mixed refrigerant' reading, what does this indicate?
Answer: The cylinder contains two or more different refrigerants blended together
A 'mixed refrigerant' failure means the cylinder contains an unintended combination of different refrigerants that cannot be separated and must be sent for destruction, not recovery.
What distinguishes R-410A from R-407C in terms of phase-change behavior during system testing?
Answer: R-410A has minimal temperature glide while R-407C has a significant glide of 4-7°F
R-410A is a near-azeotropic blend with minimal temperature glide, while R-407C is zeotropic with a temperature glide of approximately 4-7°F, which affects P-T chart readings.
What is the moisture content limit for reclaimed R-22 per AHRI Standard 700?
Answer: 10 ppm by weight
AHRI Standard 700 limits moisture in reclaimed R-22 to 10 ppm by weight to prevent ice formation in expansion devices and hydrolysis that produces corrosive acids.
What is the standard cylinder color assigned to R-12 refrigerant?
Answer: White
R-12 refrigerant cylinders are painted white per AHRI cylinder color-coding conventions, distinguishing them from R-22 (light green) and R-134a (sky blue).
What field test can be used to check for the presence of non-condensable gases in a refrigerant cylinder?
Answer: Compare cylinder pressure to the P-T chart value for the measured cylinder temperature
Non-condensable gases cause pressure to be higher than the P-T chart predicts for a given temperature because they do not condense and add to the total pressure.