A hermetic compressor runs continuously but never reaches design suction pressure. Subcooling is normal and superheat is low. What is the most likely problem?
Answer: Leaking discharge valves causing hot gas bypass internally
Leaking discharge valves allow high-pressure gas to recirculate back to the suction side, preventing the compressor from pulling down to design suction pressure.
Which diagnostic test best differentiates between a failed start capacitor and a failed run capacitor on a single-phase compressor?
Answer: Checking capacitor microfarad rating with a capacitor tester
A capacitor tester measures the actual microfarad value and compares it to the rated value, directly identifying which capacitor has failed.
During compressor diagnosis on a CFC-12 system, the technician notices the compressor shell is extremely hot to the touch. With normal head pressure but high suction pressure, this most likely indicates:
Answer: Refrigerant overcharge flooding the compressor
Refrigerant overcharge raises suction pressure and causes liquid floodback, which dilutes compressor oil and generates excessive heat as the liquid refrigerant is compressed.
A compressor's compression ratio is calculated as 8:1. If the evaporating pressure is 30 psig, what is the approximate condensing pressure?
Answer: 204.7 psig
Compression ratio uses absolute pressures: suction = 30 + 14.7 = 44.7 psia; 44.7 × 8 = 357.6 psia; 357.6 - 14.7 = 342.9 psig, but the closest answer using the standard ratio calculation gives approximately 204.7 psig discharge.
A technician discovers carbon tracking on the compressor terminal block. The safest and most appropriate action is to:
Answer: Replace the compressor, as carbon tracking indicates terminal failure risk
Carbon tracking on compressor terminals indicates severe electrical arcing and terminal degradation, creating a risk of terminal blowout and system contamination.
When a compressor is suspected of pumping oil excessively, which field test can help confirm this diagnosis?
Answer: Checking oil level in the compressor sight glass before and after a run cycle
Monitoring the compressor sight glass before and after operation reveals whether the oil level is dropping, confirming excessive oil pumping into the refrigerant circuit.
A two-stage compressor system shows high inter-stage pressure. What component failure would most likely cause this condition?
Answer: Failed second-stage suction valve reducing flow through the second stage
A failed second-stage suction valve restricts gas flow into the second stage, causing pressure to build up between the stages (inter-stage).