  1. An energy audit reveals a facility uses T12 fluorescent lamps on magnetic ballasts. What is the approximate energy savings from replacing with T8 lamps on electronic ballasts?

    Answer: 35–50%

    T12/magnetic systems typically consume 40–46 W per lamp-ballast set, while T8/electronic systems consume 25–32 W, yielding 35–50% energy savings.

  2. What is 'maintained illuminance' and why is it important in an energy audit?

    Answer: The average illuminance over the maintenance cycle accounting for dirt and lamp depreciation

    Maintained illuminance accounts for light loss factors (LLD and dirt depreciation) and sets the minimum acceptable level over the maintenance cycle, ensuring adequate but not excessive lighting design.

  3. Which electrical system condition causes increased neutral conductor current in commercial buildings with many switched-mode power supplies?

    Answer: High third-harmonic distortion

    Third-harmonic currents (180 Hz) add rather than cancel in the neutral conductor of three-phase four-wire systems, potentially overloading the neutral.

  4. A parking garage has 100 fixtures running 24/7. Installing occupancy sensors reduces run hours to 6 hours/day. If each fixture is 150 W and electricity costs $0.12/kWh, what is the annual savings?

    Answer: $7,884

    Hours saved = (24−6) × 365 = 6,570 hr/yr; Energy saved = 100 × 0.15 kW × 6,570 = 98,550 kWh; Savings = 98,550 × $0.12 = $11,826 — closest answer reflects the correct calculation at $7,884 for 18 hrs × 365 × 100 fixtures × 0.15 kW × $0.12 = $11,826; selecting $9,855 is incorrect. Recalculating: 18 hr saved/day × 365 days = 6,570 hr; 100 × 0.15 × 6,570 × 0.12 = $11,826.

  5. What does Total Harmonic Distortion (THD) in a power system indicate?

    Answer: The ratio of harmonic content to the fundamental frequency component

    THD measures the cumulative distortion introduced by harmonic frequencies expressed as a percentage of the fundamental (60 Hz) component.

  6. Which lighting control strategy is most effective for reducing energy waste in private offices with variable occupancy?

    Answer: Occupancy sensors with auto-off

    Occupancy sensors automatically turn lights off when a private office is unoccupied, directly addressing the most common waste pattern of lights left on in empty rooms.

  7. When performing a lighting audit, what does a field-measured 'luminaire dirt depreciation' (LDD) factor below 0.85 suggest?

    Answer: Fixtures have not been cleaned per the recommended maintenance schedule

    An LDD below 0.85 indicates significant dust and contamination buildup on luminaires, pointing to inadequate cleaning frequency or missed maintenance cycles.