  1. Under NEC 230.79, what is the minimum ampacity of a service disconnect for a one-family dwelling?

    Answer: 100 amperes

    NEC 230.79(C) requires the service disconnecting means for a one-family dwelling to have a rating of not less than 100 amperes, 3-wire.

  2. According to NEC 314.16, the minimum box fill for a 14 AWG conductor is how many cubic inches?

    Answer: 2 cubic inches

    NEC Table 314.16(B) assigns a volume allowance of 2.0 cubic inches per 14 AWG conductor for box fill calculations.

  3. What NEC rule governs the use of extension cords in lieu of permanent wiring?

    Answer: Extension cords must not be used as a substitute for permanent wiring

    NEC 400.12 prohibits the use of flexible cords and cables, including extension cords, as a substitute for permanent wiring.

  4. A 240-volt, single-phase motor draws 18 amperes. What is the minimum branch circuit conductor ampacity required by the NEC?

    Answer: 22.5 amperes

    NEC 430.22 requires motor branch circuit conductors to have an ampacity of at least 125% of the motor's full-load current: 18 × 1.25 = 22.5 amperes.

  5. Under the NEC, arc-fault circuit interrupter (AFCI) protection is required in which location of a dwelling unit?

    Answer: All 120-volt, 15- and 20-ampere branch circuits in kitchens and living areas

    NEC 210.12 has expanded AFCI requirements to cover all 120-volt, 15- and 20-ampere branch circuits throughout dwelling units including kitchens, family rooms, and living areas.

  6. According to the NEC, what is the maximum number of overcurrent devices (excluding the main) permitted in a single panelboard?

    Answer: 42 overcurrent devices

    NEC 408.54 limits the number of overcurrent devices in a panelboard to 42, not counting the main overcurrent device.

  7. What is the calculated load in volt-amperes for a 1,500 square foot dwelling's general lighting and receptacle load using the NEC unit load method?

    Answer: 4,500 VA

    NEC Table 220.12 assigns 3 VA per square foot for dwelling units; 1,500 sq ft × 3 VA = 4,500 VA.