Under the NEC, what is the minimum burial depth for rigid metal conduit (RMC) under a residential driveway?
Answer: 6 inches
NEC Table 300.5 specifies 6 inches minimum cover for RMC under a residential driveway.
What does the NEC require regarding GFCI protection for all 125-volt, 15- and 20-ampere receptacles in a bathroom?
Answer: All bathroom receptacles must be GFCI-protected
NEC 210.8(A)(1) requires GFCI protection for all 125-volt, 15- and 20-ampere receptacles in bathrooms.
A circuit has a resistance of 12 ohms and a voltage of 120 volts. What is the current using Ohm's Law?
Answer: 10 amperes
Ohm's Law: I = V ÷ R = 120 ÷ 12 = 10 amperes.
According to the NEC, what minimum headroom must be maintained in front of electrical equipment rated 600 volts or less?
Answer: 6.5 feet (2.0 m)
NEC 110.26(A)(3) requires a minimum headroom of 6.5 feet in front of service equipment, panelboards, and similar equipment.
Which NEC article covers grounding and bonding requirements?
Answer: Article 250
NEC Article 250 covers all grounding and bonding requirements for electrical systems.
Under the NEC, what size copper equipment grounding conductor (EGC) is required for a 60-ampere circuit?
Answer: 10 AWG
NEC Table 250.122 requires a minimum 10 AWG copper EGC for circuits protected at up to 60 amperes.
What is the power (in watts) consumed by a 10-ohm resistor carrying 5 amperes?
Answer: 250 watts
Power formula: P = I² × R = 5² × 10 = 25 × 10 = 250 watts.