Owner Training, O&M Manuals & Warranty Period Cx Flashcards
7 cards from real CCP practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Owner Training, O&M Manuals & Warranty Period Cx flashcards as text
The primary purpose of seasonal or deferred testing during the commissioning warranty period is to:
Answer: Verify system performance under operating conditions not present during initial acceptance testing
Seasonal testing captures performance data under conditions (peak heating, peak cooling, extreme humidity) that could not be evaluated when the building was initially commissioned in a different season.
Per ASHRAE Guideline 0, who is typically responsible for scheduling and coordinating seasonal testing during the warranty period?
Answer: Commissioning Authority (CxA)
The CxA retains responsibility for commissioning activities through final completion, including scheduling seasonal tests to coincide with the correct operational conditions.
A '10-month warranty review' in commissioning practice refers to:
Answer: A site visit and systems review conducted before the typical one-year contractor warranty expires
A 10-month review allows the CxA and owner to identify and document warranty-eligible deficiencies while the contractor warranty is still active, preserving the owner's right to remedy at no cost.
Issues and deficiencies discovered during warranty period commissioning activities should be formally tracked in the:
Answer: Issues Log (or Deficiency Log) maintained by the CxA
The CxA's Issues Log is the central tracking tool for all commissioning deficiencies throughout the project lifecycle, including the warranty period, ensuring accountability and resolution.
Which of the following is the most common example of a system requiring seasonal deferred testing in a heating-dominated climate?
Answer: Chiller and cooling coil performance at peak summer design conditions
In a heating-dominated climate, buildings are often commissioned in winter, so chiller and cooling systems cannot be fully load-tested until summer conditions arrive, requiring deferred seasonal testing.
During the warranty period, the Commissioning Authority's primary ongoing role is to:
Answer: Monitor system performance and coordinate resolution of identified deficiencies with responsible parties
The CxA serves as an advocate and coordinator during the warranty period, tracking performance, documenting deficiencies, and ensuring responsible parties resolve issues within the warranty timeframe.
Which document should be updated at the conclusion of warranty period commissioning to reflect changes made during that phase?
Answer: The Systems Manual, to incorporate warranty period changes and test results
The Systems Manual must be updated at warranty period close to remain accurate, incorporating any system modifications, re-calibrations, or operational changes discovered and resolved during warranty activities.