โ† All A2L Flashcard Decks

Specific Service Procedures Flashcards

6 cards from real A2L practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 Specific Service Procedures flashcards as text
  1. What is a mandatory requirement for refrigerant recovery machines and vacuum pumps used with A2L refrigerants?

    Answer: They must be certified for use with flammable refrigerants (e.g., spark-proof).

    To prevent ignition of the flammable refrigerant, all electrical equipment used for service, including recovery machines and vacuum pumps, must be specifically designed and certified for use with flammable refrigerants. This typically means they have spark-proof motors and switches.

  2. Before brazing a component on a system that contained an A2L refrigerant, what step is essential after recovery?

    Answer: Purge the system with an inert gas like nitrogen.

    Even after recovery, residual refrigerant can remain in the system oil and tubing. Purging the system with a dry, inert gas like nitrogen displaces any remaining flammable vapor and oxygen, preventing a potential fire or explosion when the brazing torch is applied.

  3. When charging a new A2L system, why is it required to charge with liquid refrigerant?

    Answer: To ensure accurate charging and prevent flammable vapor in the cylinder.

    Charging with liquid refrigerant from the cylinder prevents the fractionation of blended refrigerants and, more importantly for A2Ls, ensures that a flammable vapor is not created inside the cylinder as the pressure drops. Liquid charging is a standard safety and performance practice.

  4. After pulling a deep vacuum on an A2L system, what is the primary safety reason for breaking the vacuum with dry nitrogen?

    Answer: To prevent atmospheric air and moisture from entering the system.

    Breaking the vacuum with an inert gas like nitrogen prevents moist, oxygen-rich atmospheric air from being drawn into the system. This is crucial for system performance (preventing non-condensables and moisture) and for safety, as it avoids creating a potentially flammable air-refrigerant mixture if a leak were to occur.

  5. What is a general requirement for electronic tools, such as leak detectors or scales, when used in an area where A2L refrigerant is being serviced?

    Answer: They must be intrinsically safe or rated for flammable atmospheres.

    Any electronic tool that could create a spark must be rated as intrinsically safe or specifically designed for use in flammable atmospheres. This prevents the tool itself from becoming an ignition source in the event of a refrigerant leak during service.

  6. What should be done with service hoses immediately after charging an A2L system and closing the service valves, but before disconnecting the hoses?

    Answer: Recover the refrigerant from the hoses or use low-loss fittings.

    The refrigerant trapped in the service hoses must be managed to minimize its release to the atmosphere. This can be done by recovering the refrigerant from the hoses or using low-loss fittings to minimize the amount vented.