HVAC and Cab Systems Flashcards
6 cards from real 310T practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 HVAC and Cab Systems flashcards as text
A truck's automatic temperature control (ATC) system is cycling the compressor rapidly and the cab temperature overshoots the setpoint by 4°C before correcting. The evaporator temperature sensor reads correctly and refrigerant charge is verified. What is the MOST likely root cause?
Answer: An incorrectly calibrated blend door actuator causing hunting around the setpoint
Overshoot and hunting in an ATC system, when refrigerant charge and evaporator sensors are confirmed good, points to the blend door actuator. If the actuator's position feedback or its calibrated range is off, the control loop cannot precisely modulate airflow between the evaporator and heater core, causing the system to overcorrect repeatedly. A faulty in-car sensor would cause a sustained offset, not oscillation. Excessive charge would affect cooling capacity uniformly, not cause cycling overshoot. A corrupted PID module is possible but is a diagnosis of exclusion after mechanical causes are ruled out.
During a cab HVAC diagnosis, a technician finds that the blower motor runs at full speed regardless of the selected fan speed setting, on all speeds except OFF. The blower motor resistor pack tests open on all resistor taps. What additional test should be performed BEFORE condemning the resistor pack?
Answer: Check the blower motor ground circuit for excessive resistance that could cause resistor overheating
Blower resistor packs fail open due to overheating, and the most common cause of repeated resistor failure is a high-resistance ground in the blower motor circuit. A poor ground forces excess current through the resistors to compensate, burning them out. Simply replacing the resistor pack without checking the ground will result in repeat failure. While checking current draw and control head output are valid diagnostics, a bad ground is the primary reason a resistor pack fails on all taps simultaneously, making it the critical test before replacement.
A coach air conditioning system uses a dual-evaporator setup with a single condenser and compressor. The front evaporator cools normally, but the rear evaporator has significantly reduced cooling capacity. Both expansion valves are replaced and the refrigerant charge is correct. What is the MOST likely remaining cause?
Answer: Partial blockage in the liquid line distributor or orifice tube feeding the rear circuit
In a dual-evaporator system sharing one condenser, a restriction in the liquid line distributor or orifice feeding the rear circuit will starve that evaporator of refrigerant flow while leaving the front circuit unaffected. Since both TXVs were already replaced and charge is confirmed correct, the fault lies in distribution before the rear TXV. Oil pooling would cause a gradual efficiency reduction, not a sharp capacity drop. Air contamination accumulates at the highest point in the discharge side (condenser/receiver), not selectively in one evaporator. TXV sensing bulb loss of contact was already addressed by TXV replacement.
A technician is diagnosing a cab that has excessive humidity and fogging on the windshield even with the A/C running and defrost mode selected. The A/C compressor is confirmed operational and the evaporator core is not frozen. What is the MOST probable cause specific to the HVAC system design?
Answer: The evaporator drain tube is plugged, causing standing water to re-evaporate into the airstream
A plugged evaporator drain tube allows condensate to accumulate in the evaporator housing. As the blower pushes air over this standing water, it re-evaporates into the airstream, dramatically increasing cabin humidity despite the A/C running. This creates a self-defeating loop where the evaporator dehumidifies the air but immediately re-humidifies it from the pooled water below. A stuck recirculation door would recirculate cabin air but would not add moisture beyond what the occupants generate. A heater valve not closing fully would reduce cooling efficiency but not specifically cause re-humidification. A saturated cabin filter would restrict airflow but the evaporator would still dehumidify air passing through it.
On a truck with an engine-off auxiliary HVAC system using a dedicated scroll compressor driven by a battery bank, the system cools well for the first 45 minutes but then progressively loses capacity over the next 30 minutes until it can no longer maintain setpoint. The battery voltage remains above 12.2V throughout. What is the MOST likely cause?
Answer: Progressive thermal saturation of the condenser coil due to loss of airflow from the condenser fan motor overheating
In an APU/auxiliary HVAC system with no vehicle airflow, the condenser relies entirely on its own fan for heat rejection. If the condenser fan motor overheats due to sustained operation and thermally limits or fails progressively, the condenser cannot reject heat efficiently. As condenser temperatures rise, high-side pressure climbs, compressor work increases, and cooling capacity degrades in a predictable time-based pattern — matching the symptom. Static battery voltage above 12.2V does not rule out voltage drop under load, but that would affect compressor speed uniformly, not progressively. Refrigerant migration to the crankcase would cause slugging at startup, not 45 minutes in. The high-pressure cutout would cause abrupt cycling, not a gradual capacity reduction.
A 310T technician is retrofitting a cab HVAC system from R-134a to R-1234yf. After completing the retrofit with a POE oil flush and correct refrigerant charge, the technician notices the TXV is hunting more than before and superheat is erratic. The TXV is a universal aftermarket unit rated for both refrigerants. What is the MOST likely cause of the hunting?
Answer: The TXV sensing bulb charge is optimized for R-134a thermodynamic properties and does not respond correctly to R-1234yf suction line temperatures
A TXV sensing bulb contains a specific charge fluid matched to the thermodynamic properties of the refrigerant it controls. R-1234yf and R-134a have different pressure-temperature relationships — R-1234yf has a slightly lower saturation pressure at equivalent temperatures. A sensing bulb charged for R-134a will read the suction line temperature correctly but translate that reading into a pressure signal that corresponds to R-134a's P-T curve, causing the valve to open or close at the wrong superheat setpoint. This mismatch causes hunting and erratic superheat. Even 'dual-rated' valves require the correct sensing bulb charge for the target refrigerant. POE oil grades for both refrigerants are compatible. Residual R-134a at trace levels would reduce capacity but not cause hunting.