NEC Cheat Sheet 2026

The 30 highest-yield NEC facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.

80 questions
240 min time limit
70% to pass
  1. The continuity of a grounded conductor in a multiwire branch circuit must not depend on which connection? A device terminal such as a receptacle
  2. What size service conductors are needed for a 190 A calculated load in a dwelling? The service disconnect breaker has a 200-amp rating. 2/0 AWG
  3. What is a common cause of electrical fires? Overloaded circuits.
  4. According to the NEC, Class II hazardous locations are characterized by the presence of which hazardous substance? Combustible dust
  5. Under NEC 250.50, when multiple grounding electrodes are present at a structure, what must be done? They must all be bonded together to form a grounding electrode system
  6. What color is the equipment grounding conductor insulation typically required to be? Green or bare
  7. What is the formula for calculating electrical power in a DC circuit? P = V × I
  8. Why is it important to properly size the overcurrent protection for a branch circuit? To prevent overloading and ensure safety in case of faults.
  9. In a raceway system, what must be done when the raceway is used as a sleeve through a fire-rated wall? The raceway must be sealed with a listed fire-stop material
  10. Motor feeder tap conductors that are not more than ___ length must have an ampacity that is at least ten times the feeder protection device's rating. 10 ft
  11. How do you calculate the total amperage for a branch circuit? Dividing the total wattage by the circuit voltage.
  12. In Table 310.16, what is the ampacity of 1/0 AWG copper THHN at 90°C? 170 amps
  13. What is the minimum height clearance for overhead service-drop conductors above a residential driveway? 12 feet
  14. Per NEC 210.52, receptacle outlets in a dwelling kitchen counter are required so no point along the wall line is more than what distance from a receptacle? 24 inches
  15. Which NEC chapter contains the tables for conductor properties, conduit fill, and similar reference data? Chapter 9
  16. What is the standard burial depth for a residential 120/240V branch circuit in rigid metal conduit (RMC)? 6 in
  17. The neutral conductor in a properly wired system should be bonded to ground at: Only the service equipment/main panel
  18. When a single 20-amp branch circuit supplies the bathroom receptacles in a dwelling, what else may it supply? Only receptacles in that one bathroom
  19. Using the optional method, which load is taken at the larger of 100% of A/C or 65% of central electric heating? Heating/cooling
  20. Unless specifically permitted otherwise, what is the maximum overcurrent protection allowed for a 12 AWG copper conductor according to NEC 240.4(D)? 20A
  21. For a hotel or motel with 60 guest rooms, what demand factor does NEC Table 220.42 allow on lighting loads above 120,000 VA? 35%
  22. Which of the following should not be placed over a stairway step? overcurrent devices
  23. Which NEC requirement ensures a service disconnect can be operated without reaching over energized parts? Readily accessible location
  24. Per NEC 220.12, what is the minimum general illumination load in VA per square foot for a hospital? 2 VA/sq ft
  25. What is the main purpose of the NEC's grounding requirements? To increase the efficiency of the electrical system.
  26. GFCI protection is required for 125-volt, 15- and 20-ampere receptacles installed in which dwelling location? Garages
  27. What is the demand factor allowed for the first 3,000 VA of general lighting load in a dwelling? 100%
  28. Which NEC article covers hazardous (classified) locations? Article 500
  29. What is the standard voltage used in most residential electrical systems in the U.S.? 120 volts.
  30. According to NEC Article 100, what is the definition of 'continuous load'? A load where the maximum current is expected to continue for 3 hours or more
Turn these facts into recall:
Was this helpful?