CEI CEI Service Entrance & Metering Inspection 1 — Questions and Answers
Question 1: According to NEC 230.70, where must the service disconnecting means be located?
- Inside the main electrical panel only
- Outside the building or nearest the point of entrance of service conductors (Correct answer)
- Within 5 feet of the meter socket
- At any accessible location inside the building
Correct answer: Outside the building or nearest the point of entrance of service conductors
NEC 230.70(A)(1) requires the service disconnecting means to be installed at a readily accessible location either outside the building or inside nearest the point of entrance.
Question 2: What is the maximum number of disconnects allowed for a service entrance under NEC 230.71?
- Two disconnects per service
- Four disconnects per service
- Six disconnects per service (Correct answer)
- Eight disconnects per service
Correct answer: Six disconnects per service
NEC 230.71(A) permits a maximum of six disconnects per service, with each disconnect serving a separate load.
Question 3: During a service entrance inspection, you observe service-entrance conductors routed through the interior of a building before reaching the service equipment. Per NEC 230.6, which condition would allow this?
- The conductors are installed in a raceway
- The conductors are encased in 2 inches of concrete (Correct answer)
- The conductors are protected by a steel sleeve
- The conductors are insulated with 600V-rated insulation
Correct answer: The conductors are encased in 2 inches of concrete
NEC 230.6 considers service conductors outside a building when encased in at least 2 inches of concrete beneath a building or structure.
Question 4: What is the minimum clearance required between service-drop conductors and a roof surface with a slope of less than 4 inches in 12 inches?
- 3 feet (Correct answer)
- 8 feet
- 18 inches
- 10 feet
Correct answer: 3 feet
NEC 230.24(A) requires service-drop conductors to maintain a minimum clearance of 3 feet from the roof surface for roofs with less than a 4-in-12 slope.
Question 5: When inspecting overhead service conductors, what is the minimum clearance required above a public sidewalk?
- 10 feet
- 12 feet (Correct answer)
- 15 feet
- 18 feet
Correct answer: 12 feet
NEC 230.24(B) requires service-drop conductors to maintain a minimum vertical clearance of 12 feet above a sidewalk accessible to pedestrians.
Question 6: Which NEC section addresses the requirement that service-entrance conductors must be protected against physical damage?
- NEC 230.50 (Correct answer)
- NEC 230.54
- NEC 230.70
- NEC 230.82
Correct answer: NEC 230.50
NEC 230.50 requires service-entrance conductors to be protected against physical damage, specifying acceptable wiring methods such as rigid conduit and intermediate metal conduit.
According to NEC 230.70, where must the service disconnecting means be located?