BEE BEE Bachelor of Electrical Engineering Power Systems Engineering Questions and Answers 2 — Questions and Answers
Question 1: A 345 kV transmission line has a surge impedance of 400 ohms. What is the surge impedance loading (SIL) of the line?
- 297.6 MW (Correct answer)
- 172.5 MW
- 400 MW
- 245.3 MW
Correct answer: 297.6 MW
SIL equals V² divided by the surge impedance, so (345,000)² / 400 = 297.6 MW.
Question 2: In a power system, what is the primary purpose of a bus coupler breaker?
- To transfer load between two bus sections without interruption (Correct answer)
- To protect transformers from overvoltage
- To isolate faulty generators
- To regulate voltage at the distribution level
Correct answer: To transfer load between two bus sections without interruption
A bus coupler breaker connects two bus sections and allows load transfer between them without service interruption.
Question 3: Which type of fault in a three-phase power system typically produces the highest fault current?
- Three-phase bolted fault (Correct answer)
- Single line-to-ground fault
- Line-to-line fault
- Double line-to-ground fault
Correct answer: Three-phase bolted fault
A three-phase bolted fault produces the highest symmetrical fault current because it has the lowest impedance path.
Question 4: What does the equal area criterion determine in power system transient stability analysis?
- Whether a synchronous machine will remain in synchronism after a disturbance (Correct answer)
- The steady-state power transfer limit of a transmission line
- The optimal load dispatch between generators
- The voltage regulation of a transformer under load
Correct answer: Whether a synchronous machine will remain in synchronism after a disturbance
The equal area criterion compares accelerating and decelerating energy areas on the power-angle curve to determine if a generator maintains synchronism.
Question 5: A generator has a transient reactance of 0.25 per unit and delivers 1.0 per unit power at unity power factor. What is the internal voltage behind transient reactance?
- 1.03 per unit (Correct answer)
- 1.25 per unit
- 0.75 per unit
- 1.50 per unit
Correct answer: 1.03 per unit
The internal voltage is calculated as √(Vt² + (Xd'·I)²) = √(1² + 0.25²) ≈ 1.03 per unit at unity power factor.
Question 6: In economic load dispatch, what condition must be satisfied for optimal generation allocation among multiple units?
- The incremental cost of all participating units must be equal (Correct answer)
- Each unit must operate at its maximum efficiency point
- Total generation must equal total losses
- All units must share load equally
Correct answer: The incremental cost of all participating units must be equal
Optimal economic dispatch requires that all generating units operate at the same incremental fuel cost (lambda).
A 345 kV transmission line has a surge impedance of 400 ohms.
What is the surge impedance loading (SIL) of the line?